MOQ (minimum order quantity) PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters) RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T. We do not deliver to private end-users.
• Used to resist high and slow-blowing inrush currents up to 4000A, such as in mains protection.
Technical Specifications
Rated Voltage:
305V
Rated Breaking Capacity (@ AC250V):
1500A
Fusing Time Limits
0,08A...10A
1,25xIN, Min.:
1h
2xIN, Max.:
2min.
2,75xIN:
-
4xIN:
-
10x IN:
10ms...100ms
Part Nr.
Rated Current
Voltage
Melting
DropMax
Integral
[A]
[mV]
[A2s]
160516-0.5GT
0,16
1220
0,065
160516-1GT
0,25
840
0,19
160516-2GT
0,4
570
0,54
160516-2.5GT
0,5
490
0,86
160516-3.15GT
0,63
410
1,5
160516-4GT
1,0
380
4,5
160516-5GT
1,25
340
4,1
160516-6.3GT
1,6
330
6,2
160516-8GT
2,0
280
13
160516-10GT
2,5
240
21
REACh
REACh Art. 33: contains Lead CAS# 7439-92-1
Norms
IEC60127-4/2, UL248-14
Approvals
(E167295)
Terms of Delivery