MOQ (minimum order quantity) PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters) RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T. We do not deliver to private end-users.
Features
• Filter built in a metal housing with integrated power line connector, fuse holder and 2-pole, non-illuminated line switch • Fuse holder for two fuses 5x20mm • Screw mounting from front or rear side • FN9280_-06: for PCB mounting and faston plug terminal 6,3x0,8mm added • FN9280_-100: with spring cage terminals • FN9280B_: for medical application
Technical Specifications
Continuous Operating Voltage, Max.:
250V, 50/60Hz
Dielectric Strength, 2s
Line To Ground:
2kV AC
Line To Ground B-Type:
2,5kV AC
Line To Neutral:
0,76kV AC
Temperature Range:
-25...+85°C
Protection Class Front Side:
IP40
Rocker Switch:
Ratings:
10 (4)A/250V AC
Inrush Current:
82A
Part Nr.
IR
L
CX
CY
IL
[A]
[mH]
[nF]
[nF]
[mA]
FN9280-1-06
1
10,9
220
2,2
0,31
FN9280-2-06
2
4,4
220
2,2
0,31
FN9280-4-06
4
1,7
220
2,2
0,31
FN9280-6-06
6
0,78
220
2,2
0,31
FN9280-10-06
10
0,32
220
2,2
0,31
FN9280-10-100
10
0,32
220
2,2
0,31
FN9280B-1-06
1
10,9
220
-
0,00
FN9280B-2-06
2
4,4
220
-
0,00
FN9280B-4-06
4
1,7
220
-
0,00
FN9280B-6-06
6
0,78
220
-
0,00
FN9280B-10-06
10
0,32
220
-
0,00
FN9280B-10-100
10
0,32
220
-
0,00
IR = Rated Current, at 40°C, L = Inductance, IL = Leakage Current, Max. at 230V, 50Hz