MOQ (minimum order quantity) PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters) RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T. We do not deliver to private end-users.
Features
• Peak-/R.M.S. current limiter • Several power supplies can be installed on the same AC line • For capacitive loads • 180-264 VAC/28A continous • Internal thermal protection • Integrated bypass-relay • Capacitive load up to 6000µF • EMC Standards: EN 55032 Class B • Safety Standards: IEC 62368-1 • 3 years manufacturer warranty • ICL-28_R: DIN-Rail mounting • ICL-28_L: for installation in final equipment
Technical Specification
AC Input Range:
180...264V AC
Line Frequency:
47...63Hz
AC Continous Current:
28A
Operating Temperature Range:
-30...+70°C
Dimensions
ICL-16R:
52,5x90x54,5mm
ICL-16L:
175x42x24mm
Part Nr.
IS
CAL
Ton
TR
[A]
[µF]
[ms]
[ms]
ICL-28R
48
6000
150
100
ICL-28L
48
6000
150
100
IS = Current Limiting, Max., CAL = Capacitive Load, Max., Ton = Limiting Time ±50ms, TR = Release Time ±50ms