Logo
DE | EN Contact | About us | Terms of Business | Imprint | Privacy & Cookies | Help | Newsletter Registration | Login
 
HalbleiterOptoelektronikBauteileSunonMEAN WELLPowerSuppliesKomponentenProductNewsHerstellerBestellhinweiseKundenportalShop
Batteries
Rechargeable Batteries
Battery Chargers

NewOfferPhased outOnly on requestRoHS compliantReplace. part (not always suited)
M3400 =Product Group M3380 M3420

RECOM AC/DC Converter Modules Series RACM100

Output: 100W    Metal Case    Single Output    Input: 85 to 264VAC    Medical

Article
Part description
Manufacturer Part Number : Manufacturer
PDF PU

Price Grade

from [EUR]
MOQ
Multi
Stock & next
delivery
Procurement time Select amount

RACM100-12S

SPS Modul 100W 12V/8,34A Medical
RACM100-12S : Recom
E
1 149.94
5 140.56
10 132.29
25 123.23
1
1
0 Ø15
weeks

RACM100-15S

SPS Modul 100W 15V/6,67A Medical
RACM100-15S : Recom
E
1 149.94
5 140.56
10 132.29
25 123.23
1
1
0 Ø15
weeks

RACM100-24S

SPS Modul 100W 24V/4,17A Medical
RACM100-24S : Recom
E
1 149.94
5 140.56
10 132.29
25 123.23
1
1
0 Ø15
weeks

RACM100-48S

SPS Modul 100W 48V/2,09A Medical
RACM100-48S : Recom
E
1 149.94
5 140.56
10 132.29
25 123.23
1
1
0 Ø15
weeks
MOQ (minimum order quantity)  PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters)
RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T.
We do not deliver to private end-users.

Note
You will find suitable crimp housings NSG396M-3, NSG396M-4 and NSG396M-0 in product group F1444.
Features
• Enclosed case, crimp terminals
• Contact pin for nylon-crimp terminals
• Universal input
• Overload protection, pulsing hiccup shutdown, auto recovery
• Protections: short circuit/over load/over voltage
• Built-in active PFC function
• Low no load power consumption
• EN60601-1 compliant (2x MOPP Level)
Technical Specifications
Input Voltage:
85...264V AC (47...63Hz)
120...370V DC
Input Inrush Current, Max.:
60A
Leakage Current, Max.:
<75µA
No Load Power Consumption, Max.:
0,3W
Output Voltage Adjustment:
±10%
Over Load Protection:
115...150%
Withstand Voltage
I/P-O/P:
4000V AC
I/P-FG:
1500V AC
O/P-FG:
1500V AC
Operating Temperature:
-25...+85°C
Operating Altitude, Max.:
5000m
Weight:
210g
I/P = Input, O/P = Output, FG = Frame Ground

Part Nr.
UA
IA
PA
DUA
URN
h
  [V]
[A]
[W]
[%]
[mVp-p]
[%]
RACM100-12S 12
0...8,34
100
±1
120
91
RACM100-15S 15
0...6,67
100
±1
150
92
RACM100-24S 24
0...4,17
100
±1
160
92
RACM100-48S 48
0...2,09
100
±1
340
91
UA = Output Voltage, IA = Output Current Range, PA = Output Power, DUA = Output Voltage Tolerance, URN = Ripple & Noise, h = Efficiency
Note
These power supplies are considered as a component that has to be installed in a final equipment.
Labelling

Terms of Delivery
Minimum order quantity: 1 PKU = 1 piece
Manufacturer

http://www.recom-power.com

RACM100-_

Dimensions and Terminal Pin Assignment

Output Derating