MOQ (minimum order quantity) PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters) RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T. We do not deliver to private end-users.
Note
You will find suitable filters in product group D3213.
You will find suitable connectors here.
Features
• Universal AC input • programmable output voltage and output current • Protections: Overload / Over voltage / Over temperature • 5 years manufacturer warranty • NCP-3200-_: PMBus interface • NCP-3200-_CAN: CANBus interface • DHP-1UT-B: Chassis for NCP-3200-24 and NCP-3200-48 • DHP-1UT-BHV: Chassis for NCP-3200-380
Technical Specifications
Input Voltage:
90...264V AC (47...63Hz)
127...400V DC
Input Inrush Current, Max.:
55A
Leakage Current, Max.:
2mA
Withstand Voltage
I/P-O/P:
3000V AC
I/P-FG:
2000V AC
O/P-FG:
1500V AC
Operating Temperature:
-30... +70℃
Weight
NCP-3200-_:
2300g
DHP-1UT-_:
4760g
I/P = Input, O/P = Output, FG = Frame Ground
Part No.
UA
IA
PA
DUA
URN
h
[V]
[A]
[W]
[%]
[mVp-p]
[%]
NCP-3200-24
24
133
3192
1
300
93,5
NCP-3200-48
48
67
3216
1
480
94,5
NCP-3200-380
380
8,4
3206,4
1
4000
94
NCP-3200-24CAN
24
133
3192
1
300
93,5
NCP-3200-48CAN
48
67
3216
1
480
94,5
NCP-3200-380CAN
380
8,4
3206,4
1
4000
94
UA = Output Voltage, IA = Output Current, PA = Output Power, DUA = Output Voltage Tolerance, URN = Ripple & Noise, h = Efficiency
Note
These power supplies are considered as a component that has to be installed in a final equipment.