MOQ (minimum order quantity) PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters) RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T. We do not deliver to private end-users.
Note
You will find suitable filters in product group D3213.
You will find suitable power supply cables (export) in product group G2351.
Suitable mains cables can be found in product groups G2313, G2315 and G2319.
You will find suitable connectors here.
Suitable Camtec inrush current limiters can be found in product group M7565.
Surge protection devices can be found in product groups M7801, M7803, M7805 and M7807.
Features
• Built-in active PFC function • Output voltage and constant current level programmable • Built-in ON-OFF remote control/ alarm signal • Protections: Short circuit/ Overload/ Overvoltage/ Overtemperature/ Fan failure • Safety standards: UL 62368-1, EN 62368-1, IEC 62368-1 • EMC standards: EN55032/ EN55011 Class A/ B • 5 years manufacturer warranty • RST-7K5_: Forced air cooling • RST-7K5-_L: Water cooling
Technical Specifications
Input Voltage:
196…305 V AC (47...63 Hz)
Input Inrush Current:
75 A
Leakage Current:
3,5 mA
Over Load Protection:
100…105 %
Withstand Voltage
I/P-O/P:
4300 V DC
I/P-FG:
2800 V DC
O/P-FG:
2800 V DC
Operating Temperature:
-30...+70°C
Dimensions (LxWxH)
RST-7K5:
460x211x83,5mm
RST-7K5-L:
460x216x83,5mm
Weight
RST-7K5:
12,5 kg
RST-7K5-L:
11,9 kg
I/P = Input, O/P = Output, FG = Frame Ground
Part No.
UA
IA
PA
DUA
URN
ƞ
[V]
[A]
[W]
[%]
[mVp-p]
[%]
RST-7K5-115
115
0..65
7475
± 1
1000
94
RST-7K5-115L
115
0..65
7475
± 1
1000
94
RST-7K5-230
230
0..34,5
7452
± 1
2000
94,5
RST-7K5-230L
230
0..34,5
7452
± 1
2000
94,5
RST-7K5-380
380
0..22,5
7515
± 1
4000
95
RST-7K5-380L
380
0..22,5
7515
± 1
4000
95
UA = Output Voltage, IA = Output Current Range, PA = Output Power, DUA = Output Voltage Tolerance, URN = Ripple & Noise, h = Efficiency
Note
These power supplies are considered as a component that has to be installed in a final equipment.