MEAN WELL Switching Power Supplies Series WDR-60

DIN-Rail Assembly    Single Output    2-Phase    Power: 60W

Article
Part description
Manufacturer Part Number : Manufacturer
PDF PU

Price Grade

from [EUR]
MOQ
Multi
Stock & next
delivery
Procurement time Select amount

WDR-60-5

SPS DIN-Rail 50W 5V/10A
WDR-60-5 : MEAN WELL
E
RRP1 42.00
5 40.10
10 38.30
20 37.20
1
1
33 &
more 28/24
Ø15
weeks

WDR-60-12

SPS DIN-Rail 60W 12V/5A
WDR-60-12 : MEAN WELL
E
RRP1 42.00
5 40.10
10 38.30
20 37.20
1
1
204 &
more 20/24
Ø15
weeks

WDR-60-24

SPS DIN-Rail 60W 24V/2,5A
WDR-60-24 : MEAN WELL
E
RRP1 42.00
5 40.10
10 38.30
20 37.20
1
1
0 &
more 20/24
Ø15
weeks

WDR-60-48

SPS DIN-Rail 60W 48V/1,25A
WDR-60-48 : MEAN WELL
E
RRP1 42.00
5 40.10
10 38.30
20 37.20
1
1
1 &
more 32/24
Ø15
weeks
MOQ (minimum order quantity)  PU (Price unit): E (item), H (100 items), T (1000 items), p (pair), P (pack), k (kilogram), h (100 meters)
RRP recommended retail price. Stock and prices are updated on an hourly basis. After Registration and Login you will see your individual customer prices and CSV file upload, watchlists and requestlist are accessible in the Customer Portal. All prices are net excluding V.A.T.
We do not deliver to private end-users.

Features
• Enclosed design
• Mounted directly on the DIN rail
• Wide input range
• DC output voltage adjustable
• Built-in constant current limiting circuit
• Cooling by free air convection
• Protection: short circuit, overload, overvoltage
• Overvoltage category III
• Built-in DC OK relay contact
• Insulation class I
• Safety standards: EN61558-2-16 and more
• EMC standards: EN55032 Class B and more
• 3 years manufacturer warranty
Technical Specifications
Input Voltage:
180...550V AC (47...63Hz)
254...780V DC
Input Inrush Current, Max.:
50A
Leakage Current, Max.:
2mA
Output Voltage Adjustment:
+20%
Over Load Protection:
105...135%
Withstand Voltage
I/P-O/P:
4700V AC
I/P-FG:
2500V AC
O/P-FG:
500V AC
Operating Temperature:
-30...+85°C
Weight:
450g
I/P = Input, O/P = Output, FG = Frame Ground
Artikel
UA
IA
PA
DUA
URN
h
  [V]
[A]
[W]
[%]
[mVp-p]
[%]
WDR-60-05 5
0...10
50
2
100
83,5
WDR-60-12 12
0...5
60
1,5
120
86,5
WDR-60-24 24
0...2,5
60
1
150
89
WDR-60-48 48
0...1,25
60
1
200
90,5
UA = Output Voltage, IA = Output Current Range, PA = Output Power, DUA = Output Voltage Tolerance, URN = Ripple & Noise, h = Efficiency (Typ.)
Note
These power supplies are considered as a component that has to be installed in a final equipment.
Labelling

Terms of Delivery
Minimum order quantity: 1 PKU = 1 piece
Manufacturer

http://www.meanwell.com

WDR-60_